Electrode Steam Humidifier MiniSteam PDF Installation and Operatioan Manual
HygroMatik typically defines “normal” as feed water with a conductivity between 200 and 500 µS/ cm (microSiemens per centimeter) at 15° C.
Some areas, however, are supplied with tap water whose quality is outside the parameters specified by HygroMatik. If the HygroMatik bemis humidifier control is not adjusted correctly in these areas, the unit cannot perform optimally. For example, the electrodes could wear out particularly quickly or the steam production could be too low.
The operational parameters set by HygroMatik in the factory are intended for normal tap water. However, they can very easily be reprogrammed to fit the special requirements of a particular area. In addition, it is possible to install a plastic star in the cylinder in order to increase the life
span of the electrodes or to provide a flushing mechanism to extend maintenance intervals. Because of this you should monitor your new unit during initial operation. Make sure that it has been properly installed and is operating to your satisfaction. Consult your HygroMatik specialists. We will test the quality of your water and advise you on installation and initial operation. Your HygroMatik steam humidifier will be carefully adapted to
your particular application.
December 5, 2009 | Posted in Humidifier Manual, Electronic Manual | Leave a Comment
Humidifier Control Pdf Pdf Safety And Installation Instruction Manual
This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock.
WARNING
1.120 volts may cause serious injury from electrical shock. Disconnect electrical power to the furnace before starting installation.
2.Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling ductwork.
CAUTION
1.Do not set humidity higher than recommended. Condensation damage may result.
2.Do not set humidity up to recommended levels if there is condensation on the inside of windows of any unheated living space. Condensation damage may result.
3.Do not mount Humidifier Control on supply plenum or duct. The unit will not withstand supply temperatures.
4.When installing Humidifier Control on downflow furnaces, ensure blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the Humidifier Control.
5.Do not mount Humidifier Control downstream of the bypass outlet. False humidity conditions will cause humidifier to operate incorrectly.
December 5, 2009 | Posted in Humidifier Manual, Electronic Manual | Leave a Comment
Duct Mount Centrifugal Atomizer Humidifier PDF Manual Installation
Your centrifugal atomizer type humidifier operates on the principle of breaking down water droplets into a fine mist and atomizing the moisture into the air. If applicable, set the humidistat in the recommended range of 30-40% relative humidity for automatic humidity control during the heating season (a lower setting may be used to control condensation on single pane windows). During the first heating season, check the mineral
buildup in the humidifier every month to establish the proper cleaning schedule. Clean the unit at the end of each heating season, or whenever mineral deposits appear to be impeding the discharge of the water mist.
When shutting the humidifier down for the summer months, start with cleaning any mineral accumulation from the unit. Leave the water turned off and the unit dry. If the furnace fan is to be used for cooling purposes, disconnect power to the humidifier or turn the humidistat to
the OFF position.
December 5, 2009 | Posted in Humidifier Manual, Electronic Manual | Leave a Comment
Lennox Healthy Climate Humidified
Thank you for your recent Lennox Healthy Climate™Humidifier purchase. We sincerely appreciate your business and are pleased to add your name to our growing list of customers. Now, please take a few minutes and read this booklet. This will familiarize you with the benefits you will receive from the equipment you just purchased and help you understand the routine maintenance that will be required.
You have purchased a humidifier that operates on the evaporative principle. Itwill provide the proper relative humidity (see operating instructions) all during the heating season. It is very possible that you have questions concerning what your new humidifier can do for you, and what you should do to receive maximum benefits from it. This booklet is intended to answer these questions. The humidifier operates in conjunction with the furnace blower motor. When the humidistat calls for humidity and the blower motor is operating,water flows to the distribution pan located at the top of the unit. The water is uniformly distributed across the width of the pan and through a scientifically designed system of outlets.
December 5, 2009 | Posted in Humidifier Manual, Electronic Manual | 1 Comment